Here are the typical Full Load Amps (FLA) for 220VAC and 120VAC 1 phase 60hz electric motors.

For 230VAC 1 phase 60hz electric motors, divide the following values by 2.

They are only intended to be guidelines and in all cases, the full load amps of the motor nameplate should be used for final calculations.

Motor horsepower RPM Full Load Amps
1/20 1550 2.5
1/15 1550 2.8
1/12 1725 2.2-2.8
1550 4.1
850 3.2
1/10 1550 3.5
1050 3.4-4.2
1/8 1725 1.8-2.7
1140 3.8
1075 1.8-5.0
1/6 1725 3.3-4.7
1550 4.0-4.8
1140 4.0-4.9
1075 2.4-5.0
1/4 1725 4.4-6.3
1625 3.1-3.6
1140 5.6-6.8
1075 3.4-6.8
850 6.9
1/3 3450 5.6-6.5
1725 5.3-6.8
1140 5.0-7.2
1075 5.1
1/2 3450 9.8
1725 7.0-9.2
1075 7.3
3/4 3450 11.8
1725 11.6
1075 9.5
1 3450 13.0-15.0
1725 13.6-16.0
1-1/2 3450 16.4-19.6
1725 19.6
2 3450 19-23